Basic Info.
Max Diameter of Workpiece
<500mm
Mass Scope of Workpiece
<900kg
Type
Universal Testing Machine
Loading Method
Dynamic Load
Oil Cylinder Position
Top
Transport Package
Standard Export Package
Product Description
Accord with standard:ISO 5660 /ASTM E 1354/GB T16172
Technology data:
1.)19inch standard instrument frame,17inch touchable screen pc insert
2.)cone heater powering rating:5000w,heat output rate:0~100kw/m2
3.)in the range of 50*50mm in the center surface of expose test sample ,center irradiation error no more than +-2%;
4.)sample size:100mm*100mm*50mm
5.)weight range:0~2000g;precision:0.1g;
6.)ignition system with safe cut device high pressure spark generator ,automatic positioning
7.)clockwise magnetic oxygen analyzer ,adopt pressure change of clockwise magnetic to measure the oxygen density
8.)density range:0-25%,T90<1.5S,zero drift:<0.5%month,measure data deviation<0.5%month,
9.)non-dispersion infrared co and co2 analyzer:co:0~1%;co2:0~10%;
10.)smoke analyzer use laser system test smoke density,and this system was made up of photoelectricity two-electrode valve,0.5mv He-Ne laser,main graphics detector and auxiliary graphics detector .
11.)exhaust system was made up of fan,hottle,air intake and exhaust tube of fan and orifice meter.exhaust gas flow 0~50g/s can be adjusted,precision 0.1g/s.
12.)ring sampler need to be located in the air take tube at distance of 685mm against hottle ,need to be 12 holes existed in the sampler in order to homogeneous air flow component.
13.)exhaust gas flow need to be measured by the differencial pressure of side of hole plate above the fans at the distance of 350mm,the inner diameter of hole plate is 57mm+-1mm;
14.)the temperature of air flow is tested by armored thermocouple with closed node of diameter
Main composition of cone calorimeter:
Combustion chamber | Conical heater,10KVignition device,weighing apparatus,windshield |
Conical heater | power | 5KW |
Radiation intensity | 0-100KW/M2 |
Radiation deviation at center | ±2% |
Balance temperature of thermocouple | ±10degree |
Control thermocouple | 1.2mm armored K type,3pcs |
10KV ignition device | High voltage pulse ignition ,automatic ignition |
Radiation shielding layer | Cooling mode | Water cooling |
thickness | 11mm |
Surface Coating | Black dull |
Weighing apparatus | mileage | 2000g |
precision | ±0.05 |
Response time | <0.5S |
Drift within 30miniutes | <0.5g |
Sample mounting bracket | Upper opening 106*106mm depth 25mm |
thickness | 2.4mm |
Positioning frame | thickness | 1.9mm |
Inner edge size | 111*111 |
Specimen surface | 94*94 |
Protection cover | Half closed toughened glass cover,upper turn type open |
Gas system | Exhaust system, sampling system, smoke density measurement system, data collection system |
Sampling device | Including sampling pump,soot filter,desiccant coolingtrap,emptying bypass system ,water filter,co2 filter |
Gas collection system | Paramagnetic oxygen analyzer | Imported SIEMENS,mileage:0-25%,less than 50*10-6 within 30 miniutes |
CO analyzer | Imported SIEMENS 0-1% MILEAGE |
CO2analyzer | Imported Siemens 0-10% MILEAGE |
Smoke density measurement | Helium neon laser emitter,Double electron beam measuring device |
Ventilation system | Combustion products was exhausted from combustion chamber, standard flow rate: 0.024cubic meter/s |
| | |
Analyzer system | Including Standard instrument frame,test software,touchable industrial computer,imported sensor |
Instrument frame | 19inch standard instrument frame,9002 standard colour coating ,thickness1.5mm |
Controlled computer | 17inch touchable industrial computer,supply industrial control host |
Test software | Adjust each sensor mode,including oxygen analyzer,co2 analyzer,co analyzer,differential pressure sensor,smoke density measurement system,weighing device,single or double point adjustion of quality flow rate contro,in order to get best liner |
C- coefficient calibration, the software can automatically set the C coefficient measurement of gas flow, such as 1KW, 3KW or 5KW, the computer system automatically calculates the ISO 5660 C coefficient and the average C coefficient, and can save the record |
The software can automatically generate the C- coefficient log, which is convenient for the user to view the history of the cone calorimeter, and to identify the accuracy and stability of the system |
The system can automatically calculate the delay time of the oxygen analyzer, the carbon dioxide analyzer and the carbon monoxide analyzer, which is convenient for the synchronous calculation. |
EXCELL MODE report,can show graphics mode and data mode |
Test results include: heat release rate, flue gas flow rate, C coefficient, sample ignition time, total oxygen consumption, total oxygen consumption, mass loss rate, total heat release, effective combustion heat, carbon dioxide and carbon monoxide. |
Software was developed by America NI company standard test interface. |
sensor | Temperature sensor,heat flow meter etc. |
Heat flow :inlet water cooling type,0-100KW/m2 precision less than ±3% ,repeatability less than 0.5% |
Temperature sensor:imported from America OMEGA company |
Address:
No. 515, Hengchangjing Road, Kusshan City.
Business Type:
Manufacturer/Factory, Trading Company
Business Range:
Industrial Equipment & Components, Instruments & Meters
Management System Certification:
ISO 9000
Company Introduction:
Suzhou vouch testing technology Co., Ltd is a professional company which specialized in various flame retardance test equipment.
We focus on research&development, produce, marketing and products test service for third-party,
We have 3000 square meters standard factory and 1500 square meters test laboratory,
We support high quality and cost-effective products and professional industry solution for customers.
We have complete production supporting from sales to customer service,
We consider customer′s opinion and requirement each link,
We do best to supply good quality, safety, reliable and cost effective products to customers.
We have coopearte with Shanghai Engineer colleague, BYD Automatic company etc
Our customer industry can be find all over plastic material, chemical, fire-retardant coating, rail transit, electrical appliance, textile, electrical wire and cable, building material, cars, aircraft material, ships products, research institution and quality testing organization and so on.